Research transit power through a power network with deviations mode voltage AC traction substation
popup.stage_title
Head
Dmitriy Bosiy, д.т.н.
Registration Date
28-07-2015
Organization
Dniepropetrovsk National University of Railway Transport named after Academician V.Lazaryan
popup.description2
The experimental measurements of phase shift angle between voltage vectors of two traction substations that feed a parallel district between substations was performed. Based on measurements found that the phase angle between these vectors voltage can be up to 10 e. degrees, which in turn is the cause of active power flows, power network and additional power losses. To avoid damage from transit proposed organizational capacity to regulate transit operator of the external power supply or, alternatively install additional neutral inserts proposed the use of a flexible device with the ability to convert electric displacement vector operational voltage in the power network in the set limits.