1 documents found
Information × Registration Number 0215U008006, 0115U003919 , R & D reports Title Research transit power through a power network with deviations mode voltage AC traction substation popup.stage_title Head Dmitriy Bosiy, д.т.н. Registration Date 28-07-2015 Organization Dniepropetrovsk National University of Railway Transport named after Academician V.Lazaryan popup.description2 The experimental measurements of phase shift angle between voltage vectors of two traction substations that feed a parallel district between substations was performed. Based on measurements found that the phase angle between these vectors voltage can be up to 10 e. degrees, which in turn is the cause of active power flows, power network and additional power losses. To avoid damage from transit proposed organizational capacity to regulate transit operator of the external power supply or, alternatively install additional neutral inserts proposed the use of a flexible device with the ability to convert electric displacement vector operational voltage in the power network in the set limits. Product Description popup.authors Босий Дмитро Олексійович Косарєв Євген Миколайович Міщенко Сергій Миколайович Шама Оксана Володимирівна popup.nrat_date 2020-04-02 Close
R & D report
Head: Dmitriy Bosiy. Research transit power through a power network with deviations mode voltage AC traction substation. (popup.stage: ). Dniepropetrovsk National University of Railway Transport named after Academician V.Lazaryan. № 0215U008006