1 documents found
Information × Registration Number 0222U002657, 0117U001848 , R & D reports Title Operation of networks with non-grounded neutral popup.stage_title Head Pryshliak Yaroslava D., Кандидат технічних наук Registration Date 15-02-2022 Organization Lviv Polytechnic National University popup.description2 A study of the operation of networks with a voltage of more than 1000 V to 35 kV, including isolated or grounded through an arc-quenching reactor neutrals. It is shown that in these networks single-phase earth faults (SPEF) occur most often, most of which are arc. Arc SPEF can cause insulation breakdown of electrical equipment, as well as accelerated degradation of insulation of the entire electrically connected network. It is established that to reduce the damage to the insulation of electrical equipment, it is necessary to turn off the damaged element with the minimum possible time delay with the help of protection against SPEF. Algorithms for detecting SPEF in networks with isolated and compensated neutral for protections that respond to voltage and zero-sequence current in the transient process (at the initial moment of occurrence of SPEF), as well as recommendations for calculating the settings of such protections. Product Description popup.authors popup.nrat_date 2022-03-09 Close
R & D report
Head: Pryshliak Yaroslava D.. Operation of networks with non-grounded neutral. (popup.stage: ). Lviv Polytechnic National University. № 0222U002657